Harmonic Mitigation
Neutralizer TransMax and TransMax-Plus

Totally Integrated Power Quality

Ideal for mission-critical data centers and facilities with high concentrations of electrical loads, only the TransMax offers a four-in-one system that helps ensure maximum uptime and energy efficiency.

This revolutionary approach to power quality includes:

Blockade:
American Thermal Imaging’s proprietary harmonic suppression technology reduces the energy-wasting heat losses caused by harmonic currents and increases useable system capacity.

TP1-Energy Star Compliant Transformer:
Custom-built to American Thermal Imaging specifications, this electrostatically shielded, Energy Star-certified transformer provides maximum system efficiency. It features copper windings and a low temperature rise design. And, if your system includes a static transfer switch, a low-inrush transformer can be specified to ensure that transfer is seamless

TVSS and high-frequency noise filtering:
The TransMax-Plus goes two steps further, providing transient-voltage-surge-surpression to protect the system from voltage spikes, and EMI/RFI filtering to ensure that high frequency noise will not corrupt signals. Completely passive in operation, the TransMax contains no electronic or switching elements. That means it uses no power in operation and affects only those loads connected to it. Your entire distribution system is inoculated against excessive harmonic currents and the overloading they can cause. And by installing TransMax or TransMax-Plus in your facility, you may qualify for reduced utillity rebates and/or reduced property/casualty insurance rates.
Standard Specifications:
Neutralizer
TransMax
Neutralizer
TransMax-Plus
Blockade™ Harmonic Suppression
Enclosure UL, NEMA Type 1 UL, NEMA Type 1
Operating Temperature 0-40 degrees Centigrade 0-40 degrees Centigrade
Transformer
Enclosure UL, NEMA Type 1 UL, NEMA Type 1
Windings Input 3-phase Delta; Output 3-phase, 4-wire WYE; copper Input 3-phase Delta; Output 3-phase, 4-wire WYE; copper
Temperature Rise 115 degrees Centigrade 115 degrees Centigrade
Insulation Class 220 degrees Centigrade 220 degrees Centigrade
Mechanical Core and Coil Core and Coil
Taps 2x2.5% FCAN and FCBN 2x2.5% FCAN and FCBN
TVSS, High-Frequency Noise Filtering
Connection Means N/A Parallel
Single Pulse Surge Current Capacity N/A 160,000 Amps per Phase
Capacity per Mode N/A L-N 80,000 A
L-G 80,000 A
L-L 80,000 A
N-G 80,000 A
Surge Life Testing Category N/A C3 bi-wave per ANSI/IEEE C62.41 and ANSI/IEEE C62.25 >2,500 impulses
Protection Modes N/A 10
Noise Attenuation N/A 100kHz-34dB, 1MHz-51dB, 10MHz-54dB, 100MHz-48dB
Disconnect Means N/A Circuit Breaker

Options
Low In-Rush Transformer:
With a low in-rush transformer, TransMax can help ensure that transfer to an emergency generator in a parallel system is seamless.

Data Monitor:
Capture real-time information about your electrical system directly from your TransMax and TransMax-Plus. Our optional data monitor can provide values for power factor, total harmonic distortion, and more.
Full Load kVA Amps Rating Dimensions
H x W x D
Approximate
Weight (lbs.)
15 42 38" x 17" x 14" 230
30 83 45" x 22" x 20" 465
45 125 45" x 22" x 20" 550
75 208 55" x 26" x 21" 755
112 311 57" x 30" x 24" 1050
150 416 57" x 30" x 24" 1200
225 625 68" x 40" x 30" 2400
300 833 68" x 40" x 30" 2700
500 1388 87" x 49" x 46" 4000